Electrical connection
The electrical connection of the hob must be carried
out by qualified persons. Protection against acciden-
tal contact must be guaranteed through the appli-
ance being installed in accordance with the
regulations.
The appliance must be disconnected from the mains
during installation.
Ensure that the output of the electrical system is suf-
ficient and that the electrical cables are in good con-
dition, as well as being suitable for the current
intensity required for the cooking field. Allowance
must be made here for the other connected electrical
appliances.
The appliance must be earthed in accordance with
the regulations of the standard NF.C 15100 and the
valid regulations.
We accept no liability for accidents or incidents
caused by the lack of or a defective earth.
The mains cable must not be extended under any
circumstances. The mains connections (wall sock-
ets) must be near to the cooking field being installed.
The appliance must be disconnected from the mains
when a qualified technician is carrying out repairs.
If a crack, a rupture or a breakage can be seen on
the surface, disconnect the appliance from the
mains.
If the mains cable has to be replaced, order it from
your specialist dealer and have it replaced by a qual-
ified electrician.
Connecting the hob
The induction cooking field can be connected either
single-phase or double-phase.
Connection configurations
For the different connection possibilities, use the
brass pole jumpers which are located in the housing
next to connection terminal 1.
1st case: 1 phase, 230 V~ + N
Fit a pole jumper between the connection terminals 1
and 2.
Attach the earth to the connection terminal
x, the
neutral conductor to connection terminal 4, the
phase L either to connection terminal 2 or 1.
Case 2: 2 phases, 400 V~ + N
Attach the earth to the connection terminal
x,
Ensure that the conductors and pole jumpers are
correctly fitted and that the screws are tightened
securely.
Before connecting the appliance, it is urgently rec-
ommended to mark the phase(s), the neutral con-
ductor and the earth in the line system.
Mains voltage Connection
Minimum cross sec-
tion of the cable
Cable type Fuse rating
230 V 1N AC 1 Ph + N 4 mm H05 RR 32 A
400 V 2N AC 2 Ph + N 2.5 mm H05 RR 16 A